Software and Services for Honeywell TPS and TDC 3000
Product Information Home PageOur Price ListTechnical Support Home PageContact IAT and Our Applications SpecialistsOur Home Page

Software & Services for the Honeywell TPS & TDC 3000 distributed control systems
Quick Reference:

DataTrap
for TDC 3000

Capture
Real Time
Honeywell
TDC 3000®
Process Data
to an
ASCII File !
 Capture LCN Data to a "Manageable" ASCII File 

A low cost, easy to use, flexible tool for capturing data. Creates ASCII format text files for use in Microsoft Excel or other data analysis packages.

Capture data for performance monitoring, process troubleshooting, control loop step tests, offline tuning, etc...

One effective and convenient Display Source file used on the Universal Station or GUS Native Window allows for easy and intuitive setup of Tagnames, collection interval and duration. Collect data for up to 8 Points simultaneously.

Easy - Call up the DataTrap display and:

  • Enter the Point Tagnames.
  • Select parameters desired: PV, SP, OP and MODE.
  • Select optional Anti-Aliasing filter.
  • Select sample period (between 1 to 600 seconds).
  • Select sampling duration: max. 24 hours at Ts ³ 30 sec.; max.
  • hours at Ts < 30 sec. (actual duration may be limited at Ts = 1 or 2 seconds).
  • Select destination path & filename and select START.
Anti-Aliasing Filter - User has the option of using a First Order filter. Time constant calculated to achieve approx. -7.7 dB attenuation at the Nyquist frequency of 2×Ts (Sample Time). Takes into account any existing PV filtering detected (effective Second Order filter).
Custom Trend Display - Track all 8 points.
Online Help - HELP key provides assistance.
Free - support & software maintenance releases are provided for the life of the product.
Features:

Space-delimited ASCII files have Point.Parameter column labels & time-stamped rows
Maximum file size determined by storage media
Tagname length of 8 or 16 characters (specify choice when ordering)
Store on any LCN media (HM, Bernoulli, or Zip)
Data file uses .zz suffix
Installation & Users Guide (also in .PDF format)
User selects overwrite or append if file exists
Shipped on 150MB Bernoulli or 100MB Zip ($100 discount if ordered on 3.5" PC disk only)
Display shows message line, progression lights and data counters.
3 instances / Site License
Requirements:

  • Honeywell TDC 3000 Release 430 or later with an Application Module (AM) with FILE and CONV external load modules. Adds 2 Custom Data Segments (CDS).
  • No Background CL or AM/CL extensions required.
  • LCN file transfer device (i.e. Bernoulli or Zip drive).

Preview DataTrap sample screens (48KB).

Excel is a trademark of Microsoft Corporation. Bernoulli and Zip are trademarks of IOMEGA Corporation. TDC 3000 is a trademark of Honeywell, Inc.


Our Company policy is one of continuous development and improvement. The accuracy of these "Web" documents is not guaranteed and the right is reserved to modify, ammend or delete the contents without notice.

Last modified: November 03, 2004
© 1996